Huawei SUN2000-60KTL-M0 User Manual page 88

Three-phase grid-tied pv string inverter
Hide thumbs Also See for SUN2000-60KTL-M0:
Table of Contents

Advertisement

SUN2000-60KTL-M0
User Manual (Europe Edition)
Figure 7-5 Grid parameters (special user)
----End
Parameter List
No.
Parameter
1
Grid code
2
Output mode
3
PQ mode
4
Auto start
upon grid
Issue 02 (2018-10-15)
Vn represents the rated voltage and Fn represents the rated frequency.
Description
Set this parameter based on the
grid code of the country or region
where the SUN2000 is used and
the SUN2000 application
scenario.
Indicates whether the SUN2000
output has a neutral wire.
If this parameter is set to PQ
mode 1, the maximum active
power equals the maximum
apparent power. If it is set to PQ
mode 2, the maximum active
power equals the rated active
power.
Specifies whether to allow the
SUN2000 to automatically start
Copyright © Huawei Technologies Co., Ltd.
7 Man-Machine Interactions
Unit
Default Value
N/A
VDE-AR-N-4105
Three-phase,
N/A
four-wire
N/A
PQ mode 2
N/A
Enable
Value Range
N/A
Three-phase,
three-wire
Three-phase,
four-wire
PQ mode 1
PQ mode 2
Disable
82

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents