SUN2000-60KTL-M0
User Manual (Europe Edition)
Figure 7-7 Feature parameters (special user)
----End
Parameter List
No.
Paramete
r
1
LVRT
LVRT
2
threshold
LVRT
3
undervolta
ge
protection
shield
4
LVRT
reactive
Issue 02 (2018-10-15)
Description
When the power grid
voltage is abnormally
low for a short time,
the SUN2000 cannot
disconnect from the
power grid
immediately and has
to work for some time.
This is called LVRT.
Specifies the threshold
for triggering LVRT.
The threshold settings
should meet the local
grid standard.
Specifies whether to
shield the
undervoltage
protection function
during LVRT.
During LVRT, the
SUN2000 needs to
Copyright © Huawei Technologies Co., Ltd.
Unit
Default
Value
N/A
Enable
V
0.8 x Vn
N/A
Enable
N/A
2
7 Man-Machine Interactions
Value Range
Remarks
Disable
N/A
Enable
[0.5 x Vn, 0.92
Vn represents the
x Vn]
rated voltage.
Disable
N/A
Enable
[0, 3]
For example, if
you set LVRT
86