Setting Of Creep Speed (Dszr/Zrn Instruction; Setting Of Maximum Speed - Mitsubishi FX3G Series User Manual

Melsec-f, positioning control edition, main unit/sink output/source output, line driver output
Hide thumbs Also See for FX3G Series:
Table of Contents

Advertisement

FX
/FX
/FX
PLC User's Manual - Positioning Control Edition
3G
3U
3UC
Built-in Positioning Functions
4.2.4

Setting of Creep Speed (DSZR/ZRN Instruction)

Use the related device or the operand of the instruction to set the creep speed. The creep speed setting
range is shown in the following table.
Be sure to set the creep speed so that the relation with the other speeds is "bias speed ≤ creep speed ≤
*1
32767 Hz
".
Instruction
=Y000
D
1
DSZR
=Y001
D
1
instru-
=Y002
D
ction
1
=Y003
D
1
ZRN instruction
*1.
If the maximum speed is set to less than 32767 Hz, note that this value (32767 Hz) will automatically
be changed to the maximum speed. Furthermore, this value will automatically be changed to the zero
return speed when the zero return speed is less than the maximum speed.
*2.
Y002 (pulse output destination) cannot be specified when the 14-point or 24-point type FX
connected.
*3.
Devices related to Y003 (pulse output destination) are only valid if two FX
connected to the FX
4.2.5

Setting of Maximum Speed

Set the maximum speed to determine the upper limit value for the output pulse frequency and the zero return
speed.
Use the devices shown in the following table to determine the maximum speed for each pulse output
destination device.
Pulse output
destination device
Y000
Y001
*1
Y002
*2
Y003
*1.
Y002 (pulse output destination) cannot be specified when the 14-point or 24-point type FX
connected.
*2.
Devices related to Y003 (pulse output destination) are only valid if two FX
connected to the FX
Caution:
• To use the main unit (transistor output), set the output pulse frequency (absolute value) to 100,000 Hz or less.
If more than 100,000 Hz is output from the transistor output of the main unit to perform operation, it may cause PLC
failure.
• Set the output pulse frequency so that the output pulse frequency value is less than the maximum frequency value
of the servo amplifier (driver unit).
Setting range
Operand or
16-bit
related
operation
device
(Hz)
D8345
D8355
10 to 32767
Initial value: 1000
*2
D8365
*3
D8375
10 to 32767
S
2
PLC.
3U
Maximum
Initial value
speed
D8344,D8343
D8354,D8353
100,000Hz
D8364,D8363
D8374,D8373
PLC.
3U
4.2 Setting of Various Items Regarding Speeds
→ For operation of DSZR instruction, refer to Section 6.2.
→ For operation of ZRN instruction, refer to Section 6.3.
32-bit
operation
(Hz)
DSZR
ZRN
Setting range
Transistor output of main
unit
10 to 100,000 Hz:
If the value is set to 9 Hz or
less, the maximum speed will
be automatically set to 10 Hz.
4 Before Programming
Instruction format
S
S
D
D
1
2
1
2
S
S
S
D•
1
2
3
PLC is
3G
-2HSY-ADP adapters are
3U
High-speed output special
adapter
10 to 200,000 Hz:
If the value is set to 9 Hz or
less, the maximum speed will
be automatically set to 10 Hz.
PLC is
3G
-2HSY-ADP adapters are
3U
B - 43
A
B
Apx.