Melsec-f, positioning control edition, main unit/sink output/source output, line driver output
Hide thumbs Also See for FX3G Series:
Table of Contents

Advertisement

FX
/FX
/FX
PLC User's Manual - Positioning Control Edition
3G
3U
3UC
Example Connection
Be sure to use the class-D grounding method (grounding resistance: 100 Ω or less).
*1.
*2.
Near-point signal (DOG)
*3.
To ensure safety, use the forward rotation limit switch and the reverse rotation limit switch on both sides: the PLC side and
the servo amplifier side.
Note that the limit switches on the PLC side should be activated slightly earlier than the limit switches on the servo
amplifier side.
Reverse rotation limit 2
(Servo amplifier side)
Servo motor
*4.
To detect absolute positions, connect this line to the PLC.
Apx. - 4
Reverse rotation limit 1
Forward rotation limit 1
(Programmable
controller side)
LSR
Reverse rotation
Appendix 1. MELSERVO-J3 Series
Appendix 1-2 High-Speed Output Special Adapter
Forward rotation limit 2
(Programmable
(Servo amplifier side)
controller side)
LSF
Forward rotation