Example Connection
2. FX
PLC
3UC
FX
-32MT/D
3UC
Photo-
coupler
FX
-16EYT
2NC
FX
-16EX
2NC
Photo-
coupler
Be sure to use the class-D grounding method (grounding resistance: 100 Ω or less).
*1.
Apx. - 8
Class-D
COM
grounding
*1
X000
COM1
COM1
Y020
Servo-ON
Y021
ABS transfer mode
Y022
ABS request
Y023
Y027
COM
X020
ABS(bit0)
X031
ABS(bit1)
X032
Send data ready
X033
X037
Appendix 1. MELSERVO-J3 Series
Appendix 1-2 High-Speed Output Special Adapter
MR-J3 A
Series servo
amplifier
CN1
20
DICOM
24V DC
46
DOCOM
SON 15
ABSM 17
ABSR 18
ABSB0 22
22
ABSB1 23
23
ABST 25
ABST 25
SD
Plate