Inverter And Filters - WEG CFW-10 EASYDRIVE User Manual

Table of Contents

Advertisement

CHAPTER 3 - INSTALLATION AND CONNECTION

3.3.3 Inverter and Filters

Inverter Model
1,6A / 200-240V
2,6A / 200-240V
4,0A / 200-240V
1,6A / 110-127V
2,6A / 110-127V
Note: Maximum switching frequency is 5kHz.
Table 3.5 - List of frequency inverter models, EMC filters and EMC categories
38
+ A11 (2000). In a domestic environment this product may
cause radio interference in which case the user may be
required to take adequate measures.
6) The harmonic current emissions defined by the standards
IEC/EN61000-3-2 and EN61000-3-2 / A14 do not apply
because the CFW-10 inverter series are intended for
professional applications.
Table 3.5 shows the inverter models, its respective EMC filter
and the EMC category classification. Refer to section 3.2.2
for EMC category description and to section 3.3.4 for filter
characteristics.
Input RFI
Filter
Footprint / booksize
model:
B84142A0012R212
(EPCOS)
Standard Model:
B84142-A20-R
(EPCOS)
EMC Class
Category I (industrial environment) -
Class A1. Maximum motor cable length
is 30 meters.
Category I (industrial environment) -
Class A2. Maximum motor cable length
is 50 meters.
Category II (residential environment)
Class A1. Maximum motor cable length
is 5 meters.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents