CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
[Factory Setting]
Parameter
(1)
P266
Digital Input DI4
[ 4 - Not used (HMI)
Function-
(1)
This parameter can be changed only with disabled inverter (stopped motor).
70
Range
0 to 21
Not used
or Start/Stop
Not used (HMI) or
(Terminals) ]
General Enable (Terminals)
-
General Enable
JOG
Start/Stop
FWD/REV
Local/Remote
Multispeed
Multispeed with ramp #2
Forward run
reverse Run
FWD with ramp #2
Reverse with ramp #2
Start
Stop
Activates ramp #2
Increase EP
Decrease EP
Accelerated EP with ramp #2
Decelerates EP with ramp #2
No external fault
Error reset
Functions activated with 0V at digital input.
Description / Notes
DI Parameter
Function
NOTES!
1) Local/Remote = open/0V at the digital input
respectively.
2) P263 to P266=1 (not used or general enable)
operates as follows:
if the command source are the terminals, i.e., if
P229=1 for the local mode or P230=1 for the
remote mode, the digital input selected
operates as general enable;
otherwise, no function is assigned to the digital
input.
3) The selection of P263 to P266=16 / 17 requires
the programming of P221 and/or P222=2.
4) The selection (P263 and/or P264) and/or P265
and/or P266 = 7 / 8 (multispeed) requires the
programming of P221and/or P222=6.
DI1 (P263), DI2 (P264),
DI3 (P265), DI4 (P266)
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21