4 HMI (KEYPAD) AND BASIC PROGRAMMING

4.1 USE OF THE HMI TO OPERATE THE INVERTER

Through the HMI, it is possible to command the inverter, visualize and adjust all of its parameters.
The HMI presents two operating modes: monitoring and setting. The functions of the keys and
the fields of the display active on the HMI vary according to the operating mode. The setting
mode is composed of three levels.
- When in the setting mode, level
1: press this key to return to the
monitoring mode.
- When in the setting mode, level 2:
press this key to return to level 1 of
the setting mode.
- When in the setting mode, level 3:
press this key to cancel the new value
(new value is not saved) and return to
level 2 of the setting mode.
- When in the monitoring mode: press
this key to increase the speed.
- When in the setting mode, level 1:
press this key to go to the previous
group.
- When in the setting mode, level
2: press this key to go to the next
parameter.
- When in the setting mode, level
3: press this key to increase the
content of the parameter.
Press this key to define the motor
rotation direction.
Active when:
P0223 = 2 or 3 in LOC and/or
P0226 = 2 or 3 in REM
Press this key to commute between
LOCAL and REMOTE mode.
Active when:
P0220 = 2 or 3
CALL NOW 800-985-6929
http://www.automatedpt.com
Press this key to accelerate the motor up to the speed set in P0122 within the time determined
by the acceleration ramp. The motor speed is kept while the key is pressed. When the key is
released, the motor decelerates within the time determined by the deceleration ramp, until it
stops.
This function is active when all the conditions below are met:
1. Turn/Stop = Stop.
2. Enable general = Active.
3. P0225 = 1 in LOC and/or P0228 = 1 in REM.
http://www.automatedpt.com
HMI (Keypad) and Basic Programming
Figure 4.1: HMI Keys
Email: charles@automatedpt.com
- When in the monitoring mode: press this
key to enter the setting mode.
- When in the setting mode, level 1: press
this key to select the desired parameter
group – it shows the parameter group
selected.
- When in the setting mode, level 2:
press this key to show the parameter – it
shows the content of the parameter in
order to change the content.
- When in the setting mode, level 3: press
this key to save the new content of the
parameter – it returns to level 2 of the
setting mode.
- When in the monitoring mode: press this
key to decrease the speed.
- When in the setting mode, level 1: press
this key to go to the next group.
- When in the setting mode, level 2: press
this key to go to the previous parameter.
- When in the setting mode, level 3: press
this key to decrease the content of the
parameter.
Press this key to accelerate the motor
within the time determined by the
acceleration ramp.
Active when: P0224 = 0 in LOC or
P0227 = 0 in REM
Press this key to decelerate the motor
within the time determined by the
deceleration ramp.
Active when:
P0224 = 0 in LOC or
P0227 = 0 in REM
CFW500 | 25