[Factory Setting]
Parameter
P151
DC Link Volage
Regulation Level
(1)
This parameter can be changed only with disabled inverter (stopped motor).
CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
Range
360 to 460V
(line 110-127V)
[ 430V ]
1V
325 to 410V
(line 200-240V)
[ 380V ]
1V
Figure 6.12 - Deceleration curve with DC Link voltage regulation
Description / Notes
Ouput Voltage
P142
0
0.1Hz
Figure 6.11 - Adjustable V/F curve
The DC link voltage regulation (ramp holding) avoids in-
verter disable due to overvoltage trips (E01) during
deceleration of loads with high inertia or short
deceleration times.
It acts in order to increase the deceleration time
(according to load - inertia), thus avoiding the E01
activation.
DC Link
Voltage
P151
Rated Ud
CI Voltage
Ud (P004)
Output
Frequency
(Motor
Speed )
By this function an optimized deceleration time
(minimum) is achieved for the driven load.
This function is useful in applications with medium inertia
that require short deceleration times.
In case of overvoltage trip during the decelearation, you
must reduce gradually the value of P151 or increase the
time of the deceleration ramp (P101 and/or P103).
Output
Frequency
P145
E01 - Overvoltage
Hardware limit
Time
Time
63