3.3.1 Installation

Transformer
PE
Grounding rod
CHAPTER 3 - INSTALLATION AND CONNECTION
EMC Directive. The end user takes personal responsibility
for the EMC compliance of the whole installation. However,
when installed according to the recommendations described
in the product manual and including the recommended filters
and EMC measures the CFW-10 fulfill all requirements of the
EMC Directive (89/336/EEC) as defined by the EN61800-3
"EMC Product Standard for Adjustable Speed Electrical
Power Drive Systems - specific standard for variable speed
drives.
The conformity of the complete CFW-10 series is based on
tests performed on sample models. A Technical Construction
File (TCF) was prepared, checked and approved by a
Competent Body.
Figure 3.13 below shows the EMC filters connection.
External
input RFI
filter
L1/L
L2/N
PE
Figure 3.13 - EMC filter connection - general condition
The following items are required in order to have an
appropriated installation:
1) The motor cable shall be armored, or installed inside a
metallic conduit or trunking with equivalent attenuation.
Ground the screen/metallic conduit at both ends (inverter
and motor).
2) Control (I/O) and signal wiring shall be shielded or installed
inside a metallic conduit or trunking with equivalent
attenuation.
3) The inverter and the external filter shall be closely mounted
on a common metallic back plate. Ensure a good electrical
connection between the inverter heatsink, the filter frame
and the back plate.
4) The wiring between the filter and the inverter shall be kept
as short as possible.
XC1 1 to 12
L1
L1/L
CFW-10
L2
L2/N
PE
PE
Metallic Panel
(when necessary)
Protective Grounding
Controling and signal wiring
U
V
W
PE
Motor
35