CHAPTER 3 - INSTALLATION AND CONNECTION
P E
Q1
L/L1
N/L2
Power Supply
GROUNDING BAR
INSIDE THE PANEL
26
L/L1
N/L2
BR
+UD
Braking
Resistor
b) Models 7,3A/200-240V and 4,0A/110-127V
Figure 3.4 a) and b) - Grounding and power supply conections
DANGER!
The inverter must be grounded to a protective earth for safety
purposes (PE).
The earth or ground connection must comply with the local
regulations.For grounding, use cables with cross sections as
indicated in Table 3.3.
Make the ground connection to a grounding bar or to the ge-
neral grounding point (resistance 10 < ohms). Do not share
the ground wiring with other equipment that operate with high
currents (for instance: high voltage motors, welding machines,
etc). If several inverters are used together, refer to Figure 3.5.
Figure 3.5 - Grounding connections for more than one inverter
U
V
W
PE
PE
Shielding
V
W
U