WEG CFW-10 EASYDRIVE User Manual page 67

Table of Contents

Advertisement

[Factory Setting]
Parameter
(1)
P221
Local Reference
Selection
(1)
P222
Remore Reference
Selection
(1)
P229
Local Command
Selection
(1)
P230
Remote
Command
Selection
(1)
P231
Forward/Reverse - [ 2 - Commands]
Local/Remote
Modes
(1)
This parameter can be changed only with disabled inverter (stopped motor).
CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
Range
0 to 6
Defines the frequency reference selection in the Local and
[ 0 - keys ]
Remote mode.
-
0 to 6
[ 1 - AI1 ]
-
Define the control sources for the inverter enabling /
0 to 1
disabling FWD/REV and JOG.
[ 0 - Keys ]
-
0 to 1
[ 1 - Terminals ]
-
The direction of rotation is the only operation control that
depends on other parameter for operation - P231.
For more details, refer to Items 6.2.2, 6.2.3 and 6.2.4.
0 to 2
Description / Notes
P221/P222
0
Keys
1
Analog input AI1' (P234, P235 and P236)
2
Electronic potentiometer (EP)
3 to 5
Rerserved
6
Multispeed (P124 to P131)
AI1' is the value of the analog input AI1 when gain and
offset have been applied.
For factory default setting, the local reference is via
and
keys of the keypad and the remote
reference is via analog input AI1.
The reference value set by the
contained in parameter P121.
For more details about the Electronic Potentiometer (EP)
operation, refer to Figure 6.19.
When option 6 (multispeed) is selected, set P263-P264
and/or P265 and/or P266 to 7/8.
For more details, refer to items 6.2.2 and 6.2.4.
P229/P230
0
1
Defines the direction of rotation
P231
0
1
2
Reference Source
and
of the HMIs (P121)
and
Control source
HMI Keypad
Terminals (XC1)
Direction of rotation
Always forward
Always reverse
Commands as defined in
P229 and P230
keys is
67