CHAPTER 6 - DETAILED PARAMETER DESCRIPTION

6.3.2 Regulation Parameters - P100 to P199

[Factory Setting]
Parameter
P100
Acceleration
Time
P101
Deceleration
Time
P102
Acceleration
Time
a
2
Ramp
P103
Deceleration
Time
a
2
Ramp
P104
Ramp S
56
Range
0.1 to 999s
This set of parameters defines the time to accelerate
[ 5.0s ]
linearly from zero up to the rated frequency and to
0.1s (<100);
decelerate linearly from the rated frequency down to zero.
1s (>99.9)
The rated frequency is defined by parameter P145 .
0.1 to 999s
When factory setting is used, inverter always follows the
[ 10.0s ]
time defined in P100 and P101.
0.1s (<100);
If Ramp #2 should be used, where the acceleration and
1s (>99.9)
deceleration times follow the values programmed at
0.1 to 999s
P102 and P103, use a digital input. See parameters P263
[ 5.0s ]
to P265.
0.1s (<100);
Depending on the load inertia, too short acceleration ti-
1s (>99.9)
mes can disable the inverter due to overcurrent (E00).
0.1 to 999s
Depending on the load inertia, too short deceleration ti-
[ 10.0s ]
mes can disable the inverter due to overvoltage (E01).
0.1s (<100);
For more details, refer to P151.
1s (>99.9)
The ramp S reduces mechanical stress during the the
0 to 2
load acceleration and deceleration.
[ 0 - Inactive ]
-
It is recommended to use the S ramp with digital
frequency/speed references.
Description / Notes
P104
0
1
2
Output Frequency
(Motor Speed)
t
accel. time
(P100/102)
Figure 6.4 - S or linear Ramp
Ramp S
Inactive
50%
100%
Linear
50% ramp S
100% ramp S
t
decel. time
(P101/
103)
t (s)