1.2.2 Setting the DIL switches

Festo P.BE−CPX−FB11−EN en 0503b
When you have removed the cover for the DIL switches, you
will see five DIL switches in the field bus node (see Fig. 1/3).
DIL switch 2 is reserved for later extensions. With the other
four DIL switches you can set the following:
Operating mode and EDS mode (firmware)
Baud rate
Diagnosis mode or number of I/O bytes
Station number
Procedure:
1. Switch off the power supply.
Modifications to the DIL switch settings will not become
effective until the operating voltage is switched on again.
2. Remove the cover over the DIL switches (chapter 1.2.1).
3. Set the baud rate (lower left 2−position DIL switch).
4. Set the diagnostic mode (lower right 2−position DIL
switch).
5. Assign an unused station number to the CPX terminal.
Set the desired station number (8−position DIL switch,
elements 1...6).
6. Fit the cover again (chapter 1.2.1).
1−7