2. Commissioning
Module
Module
no.
0
Field bus node
CPX−FB11
1
Digital 8−input
module CPX−8DE
2
Digital 8−input
module CPX−8DE
3
Digital 4−output
module CPX−4DA
4
Digital multi I/O
module
CPX−8DE−8DA
5
Analogue 2−output
module CPX−2AA
6
CPA pneumatic
interface set with
DIL switch to
1 ...8 valve coils
*)
8 bits occupied 4 bits used
Tab. 2/9:
Addressing the example terminal 3 (see Fig. 2/3)
2−14
Standard EDS addressing
Input
Output
address
address
I0 ... I7
I8 ... I15
I16 ... I23
O32 ... O35
I24 ... I31
O36 ... O43
O0 ... O31
O44 ... O51
Modular EDS addressing
Input
Output
address
address
I0 ... I7
I8 ... I15
I16 ... I23
O32 ... O39
I24 ... I31
O40 ... O47
O0 ... O31
O48 ... O55