C. DeviceNet objects with Modular EDS
Attr. no.
Access
109
Get
110
Get
111
Get
112
Get
113
Get
114
Get
115
Get
116
117
118
119
120
Get/Set
121
Get/Set
122
Get/Set
C−12
Description
Diagnostic status
Specifies whether there are diagnostic data
1: There are diagnostic data
0: There are no diagnostic data
Fault number (bit 0 ... 7) (see System manual
chapter 5 Possible fault numbers")
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Monitoring (bit 0 ... 7)
Bit 0: Monitoring short circuit/overload in the
sensor supply
Bit 1: Monitoring short circuit/overload at the
outputs
Bit 2: Monitor. Vout (undervoltage at outputs)
Bit 3: Monitor. Vval (undervoltage at valves)
Bit 4: Monitor. SCV (short circuit at the valves)
Bit 5 ... 7: Reserved
1: Active (presetting)
0: Inactive
Force mode
0: Blocked
1: Enabled
Fail safe
0: Reset all outputs (presetting)
1: Hold last State (retain signal status)
2: Assume fault mode
Type
Function no.
BYTE
1937 (bit 6)
USINT
1938 (bit 0 ... 7)
SINT
SINT
SINT
SINT
SINT
BYTE
4401 (bit 0 ... 7)
USINT
4402 (bit 2, 3)
USINT
4402 (bit 0, 1)
Festo P.BE−CPX−FB11−EN en 0503b