Festo CPX-FB11 Manual page 182

Cpx terminal. cpx field bus node. field bus protocol devicenet
Hide thumbs Also See for CPX-FB11:
Table of Contents

Advertisement

C. DeviceNet objects with Modular EDS
Attr. no.
Access
109
Get
110
Get
111
Get
112
Get
113
Get
114
Get
115
Get
116
117
118
119
120
Get/Set
121
Get/Set
122
Get/Set
C−12
Description
Diagnostic status
Specifies whether there are diagnostic data
1: There are diagnostic data
0: There are no diagnostic data
Fault number (bit 0 ... 7) (see System manual
chapter 5 Possible fault numbers")
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Monitoring (bit 0 ... 7)
Bit 0: Monitoring short circuit/overload in the
sensor supply
Bit 1: Monitoring short circuit/overload at the
outputs
Bit 2: Monitor. Vout (undervoltage at outputs)
Bit 3: Monitor. Vval (undervoltage at valves)
Bit 4: Monitor. SCV (short circuit at the valves)
Bit 5 ... 7: Reserved
1: Active (presetting)
0: Inactive
Force mode
0: Blocked
1: Enabled
Fail safe
0: Reset all outputs (presetting)
1: Hold last State (retain signal status)
2: Assume fault mode
Type
Function no.
BYTE
1937 (bit 6)
USINT
1938 (bit 0 ... 7)
SINT
SINT
SINT
SINT
SINT
BYTE
4401 (bit 0 ... 7)
USINT
4402 (bit 2, 3)
USINT
4402 (bit 0, 1)
Festo P.BE−CPX−FB11−EN en 0503b

Hide quick links: