Open Style Connection (Screw Terminals, Ip20) - Festo CPX-FB11 Manual

Cpx terminal. cpx field bus node. field bus protocol devicenet
Hide thumbs Also See for CPX-FB11:
Table of Contents

Advertisement

1. Installation

1.3.5 Open Style connection (screw terminals, IP20)

Festo P.BE−CPX−FB11−EN en 0503b
The Open Style connection (type FBA−1−SL−5POL) enables the
2x5−pin terminal strip (type FBSD−KL−2x5POL) to be inserted.
The first row of connections serves to connect the incoming
field bus cable. The second row of connections serves to
connect the continuing field bus cable.
The maximum permitted current at the terminals is 4 A.
Use cables with a minimum cross−sectional area of 0.34 mm
Open Style connection
1 2
3 4
5
Tab. 1/12: Pin assignment of the field bus interface
(Open Style connection, 5−pin)
If you connect the field bus via the terminal strip type
FBSD−KL−2x5POL from Festo, you can implement a T−tap
function (double row of screw terminals).
Pin no.
1. 0 V bus
2. CAN_L
3. Screen
4. CAN_H
5. 24 V DC bus (max. 4 A)
2x5−pin terminal strip
2
.
1−21

Hide quick links: