Further Connection Possibility Via The Sub−D Connection - Festo CPX-FB11 Manual

Cpx terminal. cpx field bus node. field bus protocol devicenet
Hide thumbs Also See for CPX-FB11:
Table of Contents

Advertisement

1. Installation
1.3.7 Further connection possibility via the Sub−D connection
Pin
DeviceNet
1
n.c.
2
CAN_L
3
0 V bus
4
n.c.
5
BUS screening
6
GND optional
7
CAN_H
8
n.c.
9
24 V bus
1
5
6
9
Tab. 1/13: Pin assignment of the field bus interfaceof the CPX−FB11
Festo P.BE−CPX−FB11−EN en 0503b
After removing the Micro Style or Open Style connection, you
will find a 9−pin Sub−D plug on the top of the field bus node.
This plug offers a further connection possibility to the field
bus (supply and continuation).
Designation
Not connected
CAN Low
Power supply to the bus interface
Not connected
Capacitive connection to housing
CAN high
Not connected
Power supply to the bus interface
(View of the Sub−D plug of the CPX−FB11)
Please note
The screening connection at pin 5 of the Sub−D plug is
capacitively connected to the housing within the CPX
terminal. This prevents equalising currents from flowing
via the screening of the field bus cable (see Fig. 1/6).
Field bus plug
from Festo (IP65)
A/L
GND
Cable clip/SLD
B/H
V+
1−23