Parameter assignment/addressing
8.5 Ethernet communication
3. Enter the IP address for SIMOTION in the entry field (the default IP address is shown here).
Figure 8-11
4. Enter the desired subnet mask in the Subnet mask entry field and, if required, a router that
is to be used as default gateway.
5. Confirm with OK.
Activation state of the onboard Ethernet interfaces
The onboard Ethernet interface must be activated for the SIMOTION P Runtime (default setting
= activated).
You can check the activation via the Administration tab of SIMOTION P Control Manager
(accessible via the Windows Control Panel with Start > Settings > Control Panel).
The checkbox Activate Device is displayed after selecting the button
Ethernet Properties.
88
Changing the RT address for onboard Ethernet (1) - Properties dialog box
SIMOTION P320-4 E / P320-4 S
Commissioning and Hardware Installation Manual, 01/2015