Mounting

4.1

Installation overview

The SIMOTION P320‑4 is installed in a control cabinet or in a controller housing.
Operating mode
The following operating modes are available for a SIMOTION P320‑4:
● SIMOTION P320‑4 (headless)
● Distributed configuration of the SIMOTION P320‑4 with a remote panel.
4.2

Important information about installation

When installing the unit in an enclosed housing, make sure that sufficient space is available
for air circulation.
Ensure that the clearance to other components or the sides of cabinets is at least 50 mm above
and 100 mm below the device.
The maximum ambient temperature of the SIMOTION P320‑4 depends on the mounting
position:
● Horizontal (preferred position): Maximum +55° C (in RAL)
● Vertical (power supply at the top): Maximum +45° C
● Suspended: Maximum +40° C
● Vertical mounting: Maximum +45° C
RAL = Restricted Access Location (installation of device in operating facilities with restricted
access, for example, a locked control cabinet)
Further information can be found in the SIMOTION P320‑4 E / P320-4 S Manual.
4.3

Decentralized structure

The decentralized structure provides greater flexibility in terms of location and enables the
SIMOTION P320-4 to be positioned in non-critical areas of the plant (e.g. control cabinet).
The decentralized structure of a panel with the SIMOTION P320-4 can be performed via the
display port or DVI connection. Please note the cable lengths that are supported for the panel.
SIMOTION P320-4 E / P320-4 S
Commissioning and Hardware Installation Manual, 01/2015
4