Shunt control

In the "Shunt control" menu you choose how to control the heating of the house. Start by
deciding which sensors to use, room-/outdoor sensor or both. When you choose both, the room
sensor only works as a logger of the temperature which is shown in a curve. The room sensor
also lowers the flow temp by 5°C if max room temp is reached.
If both sensor are connected you have to choose both in the menu for the system to work.
Room sensor
If the room sensor is used it is recommended to be installed in a open space near the center
of the house. The sensor shouldn´t be influenced by draught, doors, sunlight directly to it or
other heat sources since it then will affect the heating output to the entire house.
1
Connected to number 3 on the motherboard
2
Connected to number 4 on the motherboard
3
Connected to number 5 on the motherboard
Outdoor sensor
If an outdoor sensor is used this should be mounted on the facade of the house. It is important
the sensor is mounted on the north side of the house. Make sure that the sensor isn´t disturbed
from solar gain. It is recommended that the sensor is mounted about 2 metres from ground
level and if possible protected from water and such.
1
Connected to 1 on the motherboard
2
Connected to 2 on the motherboard
36
Effecta AB - Västra Rågdalsvägen 21 - 434 99 Kungsbacka - 0300 - 22320 - info@effecta.se
Loosen the control wheel by
pulling outwards. Then loosen
the screw to open the box.
Loosen the screw and split the
casing. It is then possible to
mount the box to the wall.

Advertisement

Table of Contents
loading

Table of Contents