Trouble shooting
There are actions that the end user can take to fix a fault. However, a professional should always be
advised before doing any adjustments.
Fault
No start dose while tuning
Burner does not ignite
The display is black
Overheat protection fallshaft tripped
Ashes are totally black
Poor hot water capacity
Low/high indoor temperature
Soot in the boiler room
Alarm (flue gas), flue gases over 320ºC
No heat on radiators.
White smoke from the chimney
Convection clean does not clean
The burner tube does not get clean
The feeder does not feed pellets
A sensor shows wrong temperature
The suction system does not fill the storage
The suction system is running but no pellets comes
through the hoses
48
Effecta AB - Västra Rågdalsvägen 21 - 434 99 Kungsbacka - 0300 - 22320 - info@effecta.se
Cause
- No underpressure
- Incorrect start dose
- High draft in the chimney
- Igniter faulty
- Igniter console poorly attached
- Burner tube filled with ash
- Overheat protection fallshaft tripped
- Feeder malfunction
- Overheat protection on boiler tripped
- High back pressure in the chimney
- Burner tube filled with ash
- Poor combustion
- Low temperature in the boiler
- Too high flow in the pipes
- Too big diff between start and stop
- Incorrect temp on sensor
- Sensor untrimmed
- Improperly placed room sensor
- Improper tuned curve to outdoor sensor
- Leaking seals
- Sooty boiler
- Poor combustion
- Broken sensor
- Shunt motor closed
- Shunt motor broken
- Radiator pump not activated
- Radiator pump broken
- Air in the radiator circuit
- Low flue gas temperature
- Too big chimney
- Rain water in the chimney
- Increase the number of cleanings
- The motor does not lift turbulators
- Low pressure from compressor
- The compressor leaks
- The compressor is not activated
- No underpressure
- Feeder broken
- Feeder filled with dust
- Overheat protection fallshaft tripped
- Sensor broken
- Calibrate
- System not activated
- Proximity sensor incorrectly set
- Connection/hoses loose
- No pellets near a suction point
- The seal to the internal storage is loose
- Safety ball valve is open
- Missing screws on the storage
Action
- Seal the hole to the fallshaft
- Adust start dose
- Adjust draft stabiliser
- Change igniter
- Adjust console
- Clean the burner
- Reset
- Check feeder
- Reset protection
- Check draft
- Clean the burner
- Contact your installer
- Set the burners "Stop" temp. higher
- Adjust the flow on the mixing valve
- Reduce diff
- Adjust temp/curve to the sensor
- Calibrate the temp
- Move sensor to a suitable position
- Adjuste curve
- Contact your installer
- Clean the boiler
- Contact your installer
- Change / Contact your installer
- Contact your installer
- Contact your installer
- Activate in Shunt control
- Contact your installer
- Vent the circuit
- Cut turbulators/increase effect
- Contact your installer
- Mount a rain hood
- Increase in the Service menu
- Check function
- Check air pressure, min. (6bar)
- Seals need to be replaced
- Activate in the Service menu
- Check underpressure switch
- Check seals/hoses
- Check the draft in the chimney
- Replace motor
- Check and clean the feeder
- Clean the boiler and burner
- Reset overheat protection
- Replace sensor
- Calibrate in the Other menu
- Activate in the Installation menu
- Check and adjust sensor
- Check for leaks
- Check the pellet level in the storage
- Check the seal
- Check function
- Check that all screws is in place