EFFECTA KOMPLETT III 20-25-35 kW COMISSIONING GUIDE QUICK START GUIDE Rev. HA. 015-02-18...
Page 2
All parts and menus of this document is described in depth in the product manual. Effecta AB - Västra Rågdalsvägen 21 - 434 99 Kungsbacka - 0300 - 22320 - info@effecta.se...
Page 3
Controller setup - function test P. 18 Back end protection P. 19 Heating circuits P. 20 Heating circuits P. 21 Heating circuits P. 22 Documentation Effecta AB - Västra Rågdalsvägen 21 - 434 99 Kungsbacka - 0300 - 22320 - info@effecta.se...
Page 4
Depending on what fuel feed option the boiler is equipped with the fuel feed system needs to be completed before power up as well as the storage filled with pellets. When above is confirmed please allow electrical mains to the boiler. Effecta AB - Västra Rågdalsvägen 21 - 434 99 Kungsbacka - 0300 - 22320 - info@effecta.se...
Page 5
When pressing the touch display three icons will ap- pear. In this quick start guide you will be asked to enter the different menus in order to do different set- tings. Effecta AB - Västra Rågdalsvägen 21 - 434 99 Kungsbacka - 0300 - 22320 - info@effecta.se...
Page 6
Please leave the menu by pressing the Return key repea- tedly until the home screen appears. Effecta AB - Västra Rågdalsvägen 21 - 434 99 Kungsbacka - 0300 - 22320 - info@effecta.se...
Page 7
The calibration pro- The calibration pro- The calibration process cess is described on cess is described on is described on page page 8-9. page 12-15. 10-11. Effecta AB - Västra Rågdalsvägen 21 - 434 99 Kungsbacka - 0300 - 22320 - info@effecta.se...
Page 8
If the start dose is incorrect it will give the wrong output on the boiler which might create operational issues, excessive wear on parts and even be dangerous in extreme situations. Effecta AB - Västra Rågdalsvägen 21 - 434 99 Kungsbacka - 0300 - 22320 - info@effecta.se...
Page 9
If the feeder isn´t running it is likely that under pressure over the boiler isn´t sufficient. Make sure that the burner fall shaft is plugged at all time when the black plastic fall hose is out of the burner. Effecta AB - Västra Rågdalsvägen 21 - 434 99 Kungsbacka - 0300 - 22320 - info@effecta.se...
Page 10
If the start dose is incorrect it will give the wrong output on the boiler which might create operational issues, excessive wear on parts and even be dangerous in extreme situations. Effecta AB - Västra Rågdalsvägen 21 - 434 99 Kungsbacka - 0300 - 22320 - info@effecta.se...
Page 11
If the feeder isn´t running it is likely that under pressure over the boiler isn´t sufficient. Make sure that the burner fall shaft is plugged at all time when the black plastic fall hose is out of the burner. Effecta AB - Västra Rågdalsvägen 21 - 434 99 Kungsbacka - 0300 - 22320 - info@effecta.se...
Page 12
If the start dose is incorrect it will give the wrong output on the boiler which might create operational issues, excessive wear on parts and even be dangerous in extreme situations. Effecta AB - Västra Rågdalsvägen 21 - 434 99 Kungsbacka - 0300 - 22320 - info@effecta.se...
If the feeder isn´t running it is likely that under pressure over the boiler isn´t sufficient. Make sure that the burner fall shaft is plugged at all time when the black plastic fall hose is out of the burner. Effecta AB - Västra Rågdalsvägen 21 - 434 99 Kungsbacka - 0300 - 22320 - info@effecta.se...
Page 14
If the start dose is incorrect it will give the wrong output on the boiler which might create operational issues, excessive wear on parts and even be dangerous in extreme situations. Effecta AB - Västra Rågdalsvägen 21 - 434 99 Kungsbacka - 0300 - 22320 - info@effecta.se...
Page 15
If the feeder isn´t running it is likely that under pressure over the boiler isn´t sufficient. Make sure that the burner fall shaft is plugged at all time when the black plastic fall hose is out of the burner. Effecta AB - Västra Rågdalsvägen 21 - 434 99 Kungsbacka - 0300 - 22320 - info@effecta.se...
Page 16
Testblow start Phase out Fan pre oper. Fan low pre oper. Never use a higher output than the maximum rated output of the product! Effecta AB - Västra Rågdalsvägen 21 - 434 99 Kungsbacka - 0300 - 22320 - info@effecta.se...
Page 17
Solenoid valve Test air clean Convection clean Shunt motor 1 (+/-) Radiator pump 1 Shunt motor 2 (+/-) Radiator pump 2 Effecta AB - Västra Rågdalsvägen 21 - 434 99 Kungsbacka - 0300 - 22320 - info@effecta.se...
Page 18
Boiler warranty is void if the backend protection function isn´t activated when heating circuits are connected to the back connections of the boiler. Effecta AB - Västra Rågdalsvägen 21 - 434 99 Kungsbacka - 0300 - 22320 - info@effecta.se...
Page 19
Not recommended to use when: The building uses radiant floor heating / under floor heating. Effecta AB - Västra Rågdalsvägen 21 - 434 99 Kungsbacka - 0300 - 22320 - info@effecta.se...
Page 20
°C Recommended to use when: Any case where a separate heating controller is used. Effecta AB - Västra Rågdalsvägen 21 - 434 99 Kungsbacka - 0300 - 22320 - info@effecta.se...
Page 21
Recommended to use when: Always when a cylinder is used where a sensor can be wired back to the boiler. Hydraulic schematics For hydraulic references please see the full manual for the Komplett III. Effecta AB - Västra Rågdalsvägen 21 - 434 99 Kungsbacka - 0300 - 22320 - info@effecta.se...
Page 22
Flue boiler (if low effect On) Effect high speed Effect low speed (if activated) Back end protection Yes/No SEND A COPY TO EFFECTA: gunilla@effecta.se Effecta AB - Västra Rågdalsvägen 21 - 434 99 Kungsbacka - 0300 - 22320 - info@effecta.se...