KNX – IR Universal AC
®
IntesisBox
5.5.4 Enable use of +/- obj for Vane Up-Down
This parameter shows/hides the Control_ Vane Up-Down +/- communication object which lets you change the
indoor unit vane position by using two different datapoint types.
If set to "no" the object will not be shown.
o
If set to "yes" the Control_ Vane Up-Down +/- object.
o
➢ DPT type for +/- Vane Up-Down obj
This parameter lets choose between the datapoints 0-Up / 1-Down [DPT_1.008] and 0-Decrease / 1-
Increase [DPT_1.007] for the Control_ Vane Up-Down +/- object.
➢ Rollover Vane at upper/lower limit
This parameter lets choose if roll-over will be enabled ("yes") or disabled ("no") for the Vane Up-Down
+/- object.
Pos. 1
5.5.5 Enable use of Text object for Vane U-D
This parameter shows/hides the Status_ Vane Up-Down Text communication object.
If set to "no" the object will not be shown.
o
If set to "yes" the Status_ Vane Up-Down Text object will appear.
o
© Intesis Software S.L.U. - All rights reserved
This information is subject to change without notice
IntesisBox
®
is a registered trademark of Intesis Software SLU
Only if Roll-over is enabled
Pos. 2
Pos. 3
Only if Roll-over is enabled
▪
Up / Increase
▪
Down / Decrease
Pos. 4
Pos. 5
URL
http://www.intesisbox.com
Email
info@intesisbox.com
tel
+34 938047134
User's manual r1.0 eng
SWING
26 / 48
Need help?
Do you have a question about the IS-IR-KNX-1i and is the answer not in the manual?
Questions and answers