Scene To Execute On Bus Recovery / Startup; Enable "Lock Control" Objects; Enable Func "Operation Time Objects - IntesisBox IS-IR-KNX-1i User Manual

Hide thumbs Also See for IS-IR-KNX-1i:
Table of Contents

Advertisement

KNX – IR Universal AC
®
IntesisBox

5.1.4 Scene to execute on bus recovery / startup

This parameter executes a selected scene on bus recovery or startup, only if the selected scene has an enabled
preset or values previously saved from KNX bus (see Scene Configuration dialog). You can select any of the 5
available scenes.

5.1.5 Enable "lock control" objects

This parameter shows/hide the Control_ Lock Control Obj communication object which, depending on the sent
value, locks or unlocks ALL the Control_ communication objects except itself.
When a "1" value is sent to this communication object, the remote controller is locked. To be unlocked a "0"
value must be sent. The gateway remembers the last value received even if a KNX bus reset/failure happens.
Important: If an initial scene is enabled and it has as Value for Remote Lock (unchanged) or unlocked,
this would unlock the remote controller because the initial scene has priority over the Control_ Lock Remote
Control communication object.

5.1.6 Enable func "Operation time objects"

This parameter shows/hides the Status_ Operating Hour Counter and Status_ Operating Second Counter
communication object which counts the number of operating hours for the IS-IR-KNX-1i.
If set to "no" the object will not be shown.
o
If set to "yes" the Status_ Operation Hour Counter object will appear.
o
This object can be read and sends its status every time an hour is counted. The gateway keeps that
count in memory and the status is sent also after a KNX bus reset/failure. Although this object is
marked as a Status_ object it also can be written to update the counter when needed. To reset the
counter should be written a "0" value.
Important: This object comes by default without the write (W) flag activated. If is necessary to write on it, this
flag must be activated.
Important: This object will also return its status, every time a value is written, only if it's different from the
existing one.
Important: If the stored value is 0 hours, the gateway will not send the status to KNX.
© Intesis Software S.L.U. - All rights reserved
This information is subject to change without notice
IntesisBox
®
is a registered trademark of Intesis Software SLU
Figure 5.3
Communication object detail
Figure 5.4
Communication object detail
User's manual r1.0 eng
URL
http://www.intesisbox.com
Email
info@intesisbox.com
tel
+34 938047134
17 / 48

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the IS-IR-KNX-1i and is the answer not in the manual?

Questions and answers

Table of Contents