Enable Use Of +/- Object For Fan Speed; Enable Use Of Text Object For Fan Speed - IntesisBox IS-IR-KNX-1i User Manual

Hide thumbs Also See for IS-IR-KNX-1i:
Table of Contents

Advertisement

KNX – IR Universal AC
®
IntesisBox
If set to "no" the objects will not be shown.
o
If set to "yes" the Status_ Fan Speed objects for Speed 1, Speed 2 and Speed 3 (if available) will appear.
o
When a Fan Speed is enabled, a "1" value is returned through its bit-type object.

5.4.4 Enable use of +/- object for Fan Speed

This parameter shows/hides the Control_ Fan Speed +/- communication object which lets you
increase/decrease the indoor unit fan speed by using two different datapoint types.
If set to "no" the object will not be shown.
o
If set to "yes" the Control_ Fan Speed +/- object.
o
➢ DPT type for +/- Fan Speed Object
This parameter lets choose between the datapoints 0-Up / 1-Down [DPT_1.008] and 0-Decrease / 1-
Increase [DPT_1.007] for the Control_ Fan Speed +/- object.
➢ Roll-over Speed at upper/lower limit
This parameter lets choose if roll-over will be enabled ("yes") or disabled ("no") for the Control_ Fan
Speed +/- object.

5.4.5 Enable use of Text object for Fan Speed

This parameter shows/hides the Status_ Fan Speed Text communication object.
© Intesis Software S.L.U. - All rights reserved
This information is subject to change without notice
IntesisBox
®
is a registered trademark of Intesis Software SLU
Only if Roll-over is enabled
Fan Speed 1
Only if Roll-over is enabled
Fan Speed 2
Up / Increase
Down / Decrease
User's manual r1.0 eng
Fan Speed 3
URL
http://www.intesisbox.com
Email
info@intesisbox.com
tel
+34 938047134
23 / 48