ABB RES670 Applications Manual page 106

Relion 670 series phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

Section 6
Wide area measurement system
100
IEC140000131 V1 EN-US
Figure 43:
3PHSUM setting parameters example-showing that 3PHSUM is
using the External DFT reference coming indirectly from SMAI3
Figure
44
shows an example of wrong connection of 3PHSUM and
PHASORREPORT blocks in ACT where SMAI3 is configured as the reference
block for DFT reference external out (DFTRefExtOut) and 3PHSUM uses external
DFT reference (from SMAI3).
IEC140000132 V2 EN-US
Figure 44:
An example of wrong connection of 3PHSUM and
PHASORREPORT blocks in ACT
If settings for PMUREPORT instances (PHASORREPORT1 instances 1 and 2
above) differ for SvcClass or ReportRate, then the synchrophasor reported by
PHASOR2 connection from PHASORREPORT1 instance 2 will not be compliant
with IEEE C37.118 standard. The reason is as in the rule 2, the filtering in SMAI/
3PHSUM block is adapted according to the performance class (SvcClass) and
reporting rate of the connected instance of PHASORREPORT function block. On
the other hand, when 3PHSUM uses external DFT reference, it also adapts its
filtering according to the SMAI reference block. Therefore, in order to avoid two
1MRK 511 407-UEN C
IEC140000131-1-en
IEC140000132-2-en.vsd
Phasor measurement unit RES670 2.2 IEC
Application manual