Wide area measurement system
88
PHASORREPORT1-4, ANALOGREPORT1-3, and BINARYREPORT1-3
function blocks. In general, each instance of PMU functionality has 32
configurable phasor channels (PHASORREPORT1–4 blocks), 24 analog channels
(ANALOGREPORT1-3 blocks), and 28 digital channels (24 digital-report channels
in BINARYREPORT1-3 and 4 trigger-report channels in PMUREPORT function
block). Special rules shall be taken into account in PCM600 for Application
Configuration and Parameter Settings of multiple PMUREPORT blocks. These
rules are explained in the the Application Manual in section
Blocks Connection
Rules.
Figure
31
shows both instances of the PMUREPORT function block. As seen, each
PMUREPORT instance has 4 predefined binary input signals corresponding to the
Bits 03-00: Trigger Reason defined in STAT field of the Data frame in IEEE
C37.118.2 standard. These are predefined inputs for Frequency Trigger, Rate of
Change of Frequency trigger, Magnitude High and Magnitude Low triggers.
IEC140000118 V2 EN-US
Figure 31:
Multiple instances of PMUREPORT function block
Figure
32
shows both instances of the PHASORREPORT function blocks. The
instance number is visible in the bottom of each function block. For each instance,
there are four separate PHASORREPORT blocks including 32 configurable phasor
channels (8 phasor channels in each PHASORREPORT block). Each phasor
channel can be configured as a 3-phase (symmetrical components positive/
negative/zero) or single-phase phasor (L1/L2/L3).
IEC140000119 V2 EN-US
Figure 32:
Multiple instances of PHASORREPORT blocks
1MRK 511 407-UEN C
PMU Report Function
IEC140000118-2-en.vsd
IEC140000119-2-en.vsd
Phasor measurement unit RES670 2.2 IEC
Application manual