Section 16
Monitoring
258
31,5 MVA
110/36,75/(10,5) kV
Yy0(d5)
IEC09000040-1-EN V1 EN-US
Figure 88:
Single line diagram for transformer application
In order to measure the active and reactive power as indicated in figure 88, it is
necessary to do the following:
1.
Set correctly all CT and VT and phase angle reference channel PhaseAngleRef
data using PCM600 for analog input channels
2.
Connect, in PCM600, measurement function to LV side CT & VT inputs
3.
Set the setting parameters for relevant Measurement function as shown in the
following table 28:
110kV Busbar
200/1
P
Q
500/5
35kV Busbar
1MRK 511 407-UEN C
IED
U
L1L2
35 / 0,1kV
IEC09000040-1-en.vsd
Phasor measurement unit RES670 2.2 IEC