ABB RES670 Applications Manual page 321

Relion 670 series phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 407-UEN C
Phasor measurement unit RES670 2.2 IEC
Application manual
Function block with user defined functions in control direction, I103UserCMD.
These function blocks include the FUNCTION TYPE parameter for each block in
the private range, and the INFORMATION NUMBER parameter for each output
signal.
Status
For more information on the function blocks below, refer to the
Communication protocol manual, IEC 60870-5-103.
The events created in the IED available for the IEC 60870-5-103 protocol are
based on the:
IED status indication in monitor direction
Function block with defined IED functions in monitor direction, I103IED. This
block use PARAMETER as FUNCTION TYPE, and INFORMATION NUMBER
parameter is defined for each input signal.
Function status indication in monitor direction, user-defined
Function blocks with user defined input signals in monitor direction, I103UserDef.
These function blocks include the FUNCTION TYPE parameter for each block in
the private range, and the INFORMATION NUMBER parameter for each input
signal.
Supervision indications in monitor direction
Function block with defined functions for supervision indications in monitor
direction, I103Superv. This block includes the FUNCTION TYPE parameter, and
the INFORMATION NUMBER parameter is defined for each output signal.
Earth fault indications in monitor direction
Function block with defined functions for earth fault indications in monitor
direction, I103EF. This block includes the FUNCTION TYPE parameter, and the
INFORMATION NUMBER parameter is defined for each output signal.
Fault indications in monitor direction
Function block with defined functions for fault indications in monitor direction,
I103FLTPROT. This block includes the FUNCTION TYPE parameter, and the
INFORMATION NUMBER parameter is defined for each input signal.
This block is suitable for distance protection, line differential, transformer
differential, over-current and earth-fault protection functions.
Autorecloser indications in monitor direction
Section 19
Station communication
M17109-74 v6
315