Sensitive Directional Residual Overcurrent And Power Protection Sdepsde - ABB RES670 Applications Manual

Relion 670 series phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 407-UEN C
8.4
Phasor measurement unit RES670 2.2 IEC
Application manual
Reverse
Area
IEC10000031 V1 EN-US
Figure 59:
Relay characteristic angle given in degree
In a transmission network a normal value of RCA is about 80°.
UPolMin: Minimum polarization (reference) voltage % of UBase.
I>Dir: Operate residual current level for directional comparison scheme. The
setting is given in % of IBase. The start forward or start reverse signals can be used
in a communication scheme. The appropriate signal must be configured to the
communication scheme block.
Sensitive directional residual overcurrent and power
protection SDEPSDE
AngleRCA
Forward
Area
Iop = I2
Section 8
Current protection
Upol=-U2
IEC10000031-1-en.vsd
SEMOD171436-1 v4
147