ABB RES670 Applications Manual page 124

Relion 670 series phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

Section 7
Impedance protection
118
In a non-recoverable situation, the power swings become so severe that the
synchronism is lost: this condition is called pole slipping.
Undamped oscillations occur in power systems, where generator groups at different
locations are not strongly electrically connected and can oscillate against each
other. If the connection between the generators is too weak the magnitude of the
oscillations may increase until the angular stability is lost. More often, a three-
phase short circuit (unsymmetrical faults are much less dangerous in this respect)
may occur in the external power grid, electrically close to the generator. If the fault
clearing time is too long, the generator accelerates so much, that the synchronism
cannot be maintained even if the power system is restored to the pre-fault
configuration, see Figure 49.
1.1
3-ph
fault
260 ms
1.05
200
1-st
ms
pole-slip
1
1 corresponds
to 50 or 60 Hz
0.95
0
500
IEC10000108 V2 EN-US
Figure 49:
Stable and unstable case. For the fault clearing time tcl = 200 ms,
the generator remains in synchronism, for tcl = 260 ms, the
generator loses step.
A generator out-of-step condition, with successive pole slips, can result in damages
to the generator, shaft and turbine.
Stator windings are under high stress due to electrodynamic forces.
The current levels during an out-of-step condition can be higher than those
during a three-phase fault and, therefore, there is significant torque impact on
the generator-turbine shaft.
In asynchronous operation there is induction of currents in parts of the
generator normally not carrying current, thus resulting in increased heating.
The consequence can be damages on insulation and iron core of both rotor and
stator.
unstable
stable
← 3-rd pole-slip
← 2-nd pole-slip
← For 260 ms long 3-phase fault generator
loses synchronism. Generator operates in
asynchronous mode at speeds > nominal
← damped
oscillations
← For fault clearing time 200 ms generator remains
stable and in synchronism. After oscillations around
the nominal speed, the rotational speed returns to
the nominal, corresponding to 50 or 60 Hz
1000
1500
2000
time in milliseconds →
Phasor measurement unit RES670 2.2 IEC
1MRK 511 407-UEN C
2500
3000
IEC10000108-2-en.vsd
Application manual