ABB RES670 Applications Manual page 265

Relion 670 series phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 407-UEN C
Phasor measurement unit RES670 2.2 IEC
Application manual
Table 28:
General settings parameters for the Measurement function
Setting
Short description
Operation
Operation
PowAmpFact
Amplitude factor to scale power
calculations
PowAngComp
Angle compensation for phase
shift between measured I & U
Mode
Selection of measured current
and voltage
k
Low pass filter coefficient for
power measurement, U and I
UGenZeroDb
Zero point clamping in % of
Ubase
IGenZeroDb
Zero point clamping in % of
Ibase
UBase (set in
Base setting for voltage level in
Global base)
kV
IBase (set in
Base setting for current level in
Global base)
A
SBase (set in
Base setting for power in MVA
Global base)
Measurement function application for a generator
Single line diagram for this application is given in figure 89.
Selected
value
Off / On
On
1.000
180.0
L1L2
0.00
25
3
35.00
495
31.5
Section 16
Monitoring
Comment
On
Function must be
Typically no scaling is required
Typically no angle compensation
is required. However here the
required direction of P & Q
measurement is towards busbar
(Not per IED internal default
direction). Therefore angle
compensation have to be used in
order to get measurements in
aliment with the required
direction.
Only UL1L2 phase-to-phase
voltage is available
Typically no additional filtering is
required
Set minimum voltage level to
25%
Set minimum current level to 3%
Set LV side rated phase-to-
phase voltage
Set transformer LV winding rated
current
Set based on rated power
SEMOD54481-110 v8
259