Phasor measurement unit RES670 2.2 IEC
Application manual
IEC06000519 V2 EN-US
Figure 115:
Direct fiber optical connection between two IEDs with LDCM
The LDCM can also be used together with an external optical to galvanic G.703
converter as shown in figure 116. These solutions are aimed for connections to a
multiplexer, which in turn is connected to a telecommunications transmission
network (for example PDH).
Multiplexer
*) Converting optical to galvanic G.703
IEC05000527 V2 EN-US
Figure 116:
LDCM with an external optical to galvanic converter and a
multiplexer
When an external modem G.703 is used, the connection between LDCM and the
modem is made with a multimode fiber of max. 3 km length. The IEEE/ANSI
C37.94 protocol is always used between LDCM and the modem.

Setting guidelines

64 kbit and 2 Mbit mode common settings
ChannelMode defines how an IED discards the LDCM information when one of
the IEDs in the system is out of service: it can either be done on the IED out of
service by setting all local LDCMs to channel mode OutOfService or at the remote
end by setting the corresponding LDCM to channel mode Blocked. If OutOfService
Telecom. Network
*)
Section 20
Remote communication
en06000519-2.vsd
Multiplexer
en05000527-2.vsd
*)
M12454-3 v7
325