Setting Guidelines; Setting Procedure On The Ied - ABB RES670 Applications Manual

Relion 670 series phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 407-UEN C
16.4.3
16.4.3.1
Phasor measurement unit RES670 2.2 IEC
Application manual

Setting guidelines

The breaker monitoring function is used to monitor different parameters of the
circuit breaker. The breaker requires maintenance when the number of operations
has reached a predefined value. For proper functioning of the circuit breaker, it is
also essential to monitor the circuit breaker operation, spring charge indication or
breaker wear, travel time, number of operation cycles and accumulated energy
during arc extinction.
Since there is no current measurement in SAM600-IO, evaluation
of the following parameters are not possible in the circuit breaker
condition monitoring function (SSCBR):
Circuit breaker status
Remaining life of the circuit breaker
Contact erosion estimation
Circuit breaker contact travel time
Ensure that OPENPOS, CLOSEPOS, INVDPOS, CBLIFEAL,
IPOWALPH, IPOWLOPH, TRVTOPAL and TRVTCLAL signals
are not used in SAM600–IO.

Setting procedure on the IED

The parameters for breaker monitoring (SSCBR) can be set via the local HMI or
Protection and Control Manager (PCM600).
Common base IED values for primary current (IBase), primary voltage (UBase)
and primary power (SBase) are set in Global base values for settings function
GBASVAL.
GlobalBaseSel: It is used to select a GBASVAL function for reference of base
values.
Operation: On or Off.
IBase: Base phase current in primary A. This current is used as reference for
current settings.
OpenTimeCorr: Correction factor for circuit breaker opening travel time.
CloseTimeCorr: Correction factor for circuit breaker closing travel time.
tTrOpenAlm: Setting of alarm level for opening travel time.
tTrCloseAlm: Setting of alarm level for closing travel time.
OperAlmLevel: Alarm limit for number of mechanical operations.
Section 16
Monitoring
GUID-AB93AD9B-E6F8-4F1A-B353-AA1008C15679 v3
GUID-4E895FEA-74BF-4B11-A239-0574F8FF5188 v5