Section 18
Ethernet-based communication
18.2.3
288
Device 1
AP1
PhyPortA
PhyPortB
PhyPortB
PhyPortA
AP1
Device 3
IEC16000038 V1 EN-US
Figure 95:
High-availability Seamless Redundancy (HSR)

Setting guidelines

Redundant communication is configured with the Ethernet configuration tool in
PCM600.
Redundancy: redundant communication is activated when the parameter is set to
PRP-0, PRP-1 or HSR. The settings for the next access point will be hidden and
PhyPortB will show the second port information. Redundant communication is
activated after a common write to IED is done.
PRP-1 should be used primarily, PRP-0 is intended only for use in existing PRP-
networks. PRP-1 and HSR can be combined in a mixed network.
If the access point is not taken into operation, the write option in Ethernet
Configuration Tool can be used to activate the access point.
Device 2
AP1
PhyPortA
PhyPortB
PhyPortB
PhyPortA
AP1
Device 4
IEC16000038-1-en.vsdx
Phasor measurement unit RES670 2.2 IEC
1MRK 511 407-UEN C
GUID-887B0AE2-0F2E-414D-96FD-7EC935C5D2D8 v1