ABB RES670 Applications Manual page 59

Relion 670 series phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 407-UEN C
Phasor measurement unit RES670 2.2 IEC
Application manual
IEC06000196 V2 EN-US
Figure 10:
Example how to set CTStarPoint parameters in the IED
For busbar protection, it is possible to set the CTStarPoint parameters in two ways.
The first solution will be to use busbar as a reference object. In that case for all CT
inputs marked with 1 in Figure 10, set CTStarPoint = ToObject, and for all CT
inputs marked with 2 in Figure 10, set CTStarPoint = FromObject.
The second solution will be to use all connected bays as reference objects. In that
case for all CT inputs marked with 1 in Figure 10, set CTStarPoint = FromObject,
and for all CT inputs marked with 2 in Figure 10, set CTStarPoint = ToObject.
Regardless which one of the above two options is selected, busbar differential
protection will behave correctly.
Busbar
Busbar
Protection
1
IED
2
Section 4
Analog inputs
2
1
1
en06000196.vsd
53