Hydran* M2-X Instruction Manual
WARNING
Note: The external ac power supply range is 110 Vac ± 15 % or 230 Vac ± 15 %, and
from 47 to 63 Hz.
6. Power up the Hydran M2-X. The Main Menu should be displayed.
7. Wait for five minutes or press the Esc key to switch to the Main Display mode
(see Section 3.1.2.3). Observe the various readings in each of the three
screens; it is normal for certain values to be low.
8. Wait a few minutes and touch the heater plate; it should be warm.
9. Proceed as follows to confirm keypad operation:
• Press the Main Menu context key. The Main Menu should be displayed.
• Click the Down arrow key two times to highlight Setup and press the Enter
context key.
• Try each arrow key and verify if the "cursor" moves in the corresponding
direction.
10. Make a shadow over the Hydran M2-X's display and verify the backlighting
is functioning. The display should be readable under all ambient lighting
conditions.
4.2.2
Setting the Date and Time
1. Access Setup > Date & Time.
2. If necessary, set parameters Current Date and Current Time to local values.
4.2.3
Verifying the Sensor's Serial Number
1. Access Service > Sensor Param > Gas Sensor Param and press Enter.
2. Compare the serial number displayed on the screen with the one engraved
under the sensor's connector (see item 5 in Figure 2-7).
3. Press Esc to return to the previous level, select H
Enter.
4. Again, compare the serial number displayed on the screen with the one
engraved under the sensor's connector.
4.2.4 Verifying the State of the Gas Detector
MA-029
Rev. 1.0, 30-Jul-18
Turn off the electric power at the switch or circuit
breaker provided for disconnection before making any
electrical connections, and ensure a proper ground
connecting is made before connecting line voltage.
Failure to do so can result in property damage,
personal injury and/or death.
O Sensor Param and press
2
Page 69