GE Hydran M2-X Instruction Manual page 176

Transformer gas monitoring system
Hide thumbs Also See for Hydran M2-X:
Table of Contents

Advertisement

Terminal
Description
L
Line
Neutral
N
Enclosure
ground
(Earth)
Connect a ground wire to the external terminal lug. Use a 10-6 AWG (approximately 5.3 – 13.3
1.
mM2-X) copper wire.
WARNING
Page 176
From (External)
Live side of AC supply
Other side of AC supply
Unless otherwise required
by the application local
regulations, the ground wire
from the power supply
cable must not be
connected to this terminal
Table D - 4: Connections for the AC Power Supply Terminal Block
Not connecting the ground terminal will cause operational
failure.
Hydran* M2-X Instruction Manual
Comments
AC supply is 110Vac ±15%
or 230Vac ±15% and from
47 to 63Hz. Maximum
load is 4A.
Use external ground lug
instead
a
MA-029
Rev. 1.0, 30-Jul-18