Replacing The Battery; Battery Specification - GE Hydran M2-X Instruction Manual

Transformer gas monitoring system
Hide thumbs Also See for Hydran M2-X:
Table of Contents

Advertisement

WARNING
Fuse specifications:
• GE part number: 16426
• Fuse size: 5 x 20 mm
• Fuse type: Time delay
• Fuse rating: 4A, 250V
• Recommended models: 0218004.MXP (Littelfuse), S506-4-R (Bussman)

9.3 Replacing the Battery

The battery is used to keep the real-time clock functioning and to retain the
historic data when the Hydran M2-X unit is not powered.
Every five years, it is recommended to replace the Lithium battery used in the
unit.
Note: When the battery becomes too weak, an alarm message will be displayed and
broadcast. In this case, the battery has to be replaced as soon as possible.
WARNING
9.3.1

Battery Specification

For Hydran M2-X units built as from 2013 (S/N: 13xxxxxxxx), the battery
specifications are the following:
• GE part number: 18670.
• Battery size and type: 1/2AA, Lithium 3.6 V, 1.2 Ah.
• Battery life: Five years (RTC backup).
• Recommended model: SB-AA02 (Vitzro Cell), ER14250/W (OmniCel), TL-
5276/W (Tadiran).
For Hydran M2-X units built prior to 2013, the battery specifications are:
• Type: Lithium cell.
• Diameter: 17.0 mm.
• Length: 33.5 mm.
• Nominal voltage: 3V.
• Nominal capacity: 1,200 mAh.
• Recommended model: Panasonic BR-2/3A.
Page 136
The replacement of the fuse must be executed by trained
service personnel only.
The replacement of the battery must be executed by trained
service personnel only.
procedure.
Hydran* M2-X Instruction Manual
Refer to Appendix G for the
MA-029
Rev. 1.0, 30-Jul-18