Hydran* M2-X Instruction Manual
4.4.2 Setting the Parameters of the History Files
1. Access Setup > History Setup > History Log Rate (see Section 3.2.6.1).
2. Verify and set, as required, the Short Term Rate as well as the Long Term #1
to Long Term #4 logging hours.
3. Press Esc, select Clear HM2-X Hist File and press Enter.
4. Erase the content of the history files by selecting each option and pressing
Ok.
4.4.3 Setting the Alarm Parameters
1. Wait at least 30 minutes after powering up the Hydran M2-X or until the gas
and moisture levels read by the Hydran M2-X are stable.
2. Access Alarms > Alarms Setup > Hydran Alarm Setup (see Section 3.3.2.1).
Verify and set, as required, all parameters.
3. Access Alarms > Alarms Setup > H2O Alarm Setup (see Section 3.3.2.2).
Verify and set, as required, all parameters.
4. Access Alarms > Alarms Setup > Temp Alarm Setup (see Section 3.3.2.3).
Verify and set, as required, all parameters.
5. Access Alarms > Alarms Setup > Battery Alarm Setup (see Section 3.3.2.4).
Verify and set, as required, all parameters.
6. Access Alarms > Alarms Setup > Analog Input Alarm Setup (see Section
3.3.2.5). Verify and set, as required, all parameters.
7. Access Alarms > Alarms Setup > Sys. Fault Trigger (see Section 3.3.2.6).
Verify and set, as required, all parameters.
4.4.4 Verifying the Battery Voltage
1. Access Service > View Service Data.
2. Verify the battery voltage (Battery) exceeds 2.85 V; if it is below 2.85 V, replace
the battery (see Appendix G). For the battery specifications, see Section 9.3.1.
4.4.5 Setting the Dynamic Oil Sampling System Parameters
1. Access Setup > Temp. Setup (see Section 3.2.4).
2. Verify and set, as required, the dynamic oil sampling system parameters. For
more information, see Section 3.2.4.
3. Clear the Sensor Hist File.
MA-029
Rev. 1.0, 30-Jul-18
Page 93