Verifying And Setting The Battery Alarm Parameters; Logging The Values Of The Service Data; Verifying And Setting The Date And Time; Verifying And Setting The Communications Parameters - GE Hydran 201i Instruction Manual

Transformer gas monitoring system
Hide thumbs Also See for Hydran 201i:
Table of Contents

Advertisement

Hydran* 201i Instruction Manual
5. Push ENTER. The message Are You Sure?; Press Enter.. is now displayed.
6. Push ENTER again to confirm.
7. When asked to enter the password #1 (1253), use the UP and ENTER keys.
8. The message Please wait... appears, the test is executed (during a four-second
countdown), and the Hydran 201Ti's display should indicate the message Good. If
another message is displayed, see Section 13.1.3.
Note: The keypad cannot be used for two minutes following a sensor test. Wait before
resuming the configuration.

7.4.7 Verifying and Setting the Battery Alarm Parameters

1. Access the submenu H201Ti Vx.xx;Service.
2. Access the submenu Service;Battery.
3. Verify the battery voltage (Battery). For details, see Section 7.1.4.
4. Verify and set, as required, the three alarm parameters.

7.4.8 Logging the Values of the Service Data

1. Access the submenu H201Ti Vx.xx;Service.
2. Access the submenu Service;ServiceData.
3. Write down the value of each parameter.

7.4.9 Verifying and Setting the Date and Time

For details on the parameters and commands in the submenu Date&Time, see Section
5.5.5.
1. Access the submenu H201Ti Vx.xx;Date&Time.
2. If required, set the parameters Year, Month, Day, Hour and Minutes to local
values.

7.4.10 Verifying and Setting the Communications Parameters

For details on the parameters and commands in the submenu Communication, see
Section 5.5.6.
1. Access the submenu H201Ti Vx.xx; Communication.
2. Verify and set, as required, the eight communication parameters (which can only
be accessed from the Hydran 201Ti's keypad). Note the following considerations:
• Gas Monitor ID (identification number of the H201Ti): At least one H201Ti in
the local network must be set to an identification number from 1 to 5
inclusively. Each H201Ti in the local network must have an exclusive number
from 1 to 254.
MA-033
Rev. 14.0, 12-Nov-18
Page 119