GE Hydran M2-X Instruction Manual page 178

Transformer gas monitoring system
Hide thumbs Also See for Hydran M2-X:
Table of Contents

Advertisement

Terminal
Relay
a
1
1
2
3
4
2
5
6
7
3
8
9
10
4
11
12
13
5
14
15
a. Designed for 16-14 AWG (1.37-2.03 mM2-X) wires
b. Electric specifications for all relays: 125 VA @ 250 Vac, 60 W @ 220 Vdc
c.
NC = Normally Closed (contact is closed when the relay is not energized);
NO = Normally Open (contact is open when the relay is not energized)
Page 178
Description
b
c
NO
SCADA system, Hydran
201Ci-1 or Hydran
Common
201Ci-4
NC
NO
Common
NC
NO
Common
NC
NO
Common
NC
NO
Common
NC
Table D - 5: Connections for the Alarm Contacts Terminal Block
Hydran* M2-X Instruction Manual
To (External)
User-configurable;
normally assigned to
gas High alarms
User-configurable;
normally assigned to
gas High-High alarms
User-configurable;
normally assigned to
moisture High alarms
User-configurable;
normally assigned to
moisture High-High
alarms
Not configurable;
used only for alarms
due to system fault
conditions; NO is
closed if system is OK,
NC is open if system
fails
Comments
MA-029
Rev. 1.0, 30-Jul-18