4.4.6 Setting the Readings Parameters
1. Access Setup > Readings Setup > Gas Reading Setup (see Section 3.2.8.1).
Verify and set, as required, the gas reading parameters.
2. Press Esc and access H2O Reading Setup (ses Section 3.2.8.2). Verify and set,
as required, the parameters for the moisture and relative humidity average
calculation.
3. Press Esc; verify and set, as required, the Sens. Temp Avg Per. parameter
(used for the temperature average calculation of the sensor).
4.4.7 Configuring the Analog Input(s) (If Used)
1. Access Service > System Config > Current Config. Verify that the displayed
list corresponds to the Hydran M2-X configuration. If not, access Service >
System Config > Detected Config; the Hydran M2-X detects the installed
configuration. Press Save to reboot the Hydran M2-X.
2. Access Setup > I/O Setup > Analog In Setup (see Section 3.2.9.1).
Note: The following steps must be performed for each analog input interface.
3. Select the analog input interface to configure; the corresponding parameter
screen is now displayed.
4. Make sure Input Range is set to 4–20 mA.
Note: Analog input interfaces are calibrated at the factory for a 0–20 mA
range. However, when parameter Input Range is set to 4–20 mA, the interface
automatically adapts to this range.
5. In the parameter screen, scroll down the list of parameters and select option
Configuration. The Configuration screen is now displayed.
6. Select Identification and set all parameters as desired.
7. Press Esc to return to the Configuration screen and select Readings Setup.
Set all parameters as required.
8. Perform the verification procedure described in Section 4.2.8.
4.4.8 Configuring the Analog Output(s) (If Used)
1. Access Service > System Config > Current Config. Verify that the displayed
list corresponds to the Hydran M2-X configuration. If not, access Service >
System Config > Detected Config; the Hydran M2-X detects the installed
configuration. Press Save to reboot the Hydran M2-X.
2. Access Setup > I/O Setup > Analog Out Setup (see Section 3.2.9.2).
Note: The following steps must be performed for each analog output interface.
3. Select the analog output interface to configure, and then select the option
Configuration. The Configuration screen is now displayed.
4. Set all parameters as required.
Page 94
Hydran* M2-X Instruction Manual
MA-029
Rev. 1.0, 30-Jul-18
Need help?
Do you have a question about the Hydran M2-X and is the answer not in the manual?
Questions and answers