C Ode (C Ontinued ) - Elster A1140 User Manual

Programmable electronic polyphase meter
Table of Contents

Advertisement

42
A1120/40 - Electronic Polyphase Meter
VERSION
8 TOU Registers, 4 MD Registers, 15 Historical Registers, DSM - see Note 4
8 TOU Registers, 4 MD Registers, 15 Historical Registers, DSM, DLS time stamps and 12 external registers - Note! All new customers from November 2007 - see
Note 4
8 TOU Registers, 4 TOU Registers, 15 Historical Registers, DSM, DLS Time stamps, 12 External Registers and Daily Billing
8 TOU Registers, 4 TOU Registers, 15 Historical Registers, DSM, DLS Time stamps, 12 External Registers - Note! Register zeroing by use of "Register Zeroing Tool"
is NOT available in this option
Revision Suffix
Firmware 2-01178-Q (Version A only). Enhanced GPRS and COP 10
Firmware 2-01322-K (Version C) Enhanced GPRS and COP 10
Firmware 2-01340-B (Version F) Daily Billing
Firmware 2-01345-A (Version G) Enhanced GPRS & COP 10. No register zeroing
SPECIAL ADDITIONS FIRMWARE
None
Additional Firmware Function for ESCOM only (Phase angle definition as A1700
SPECIAL ADDITIONS HARDWARE
NONE
Notes
Note 1: CURRENT RATINGS
IEC/EN 62052-11 defines only Basic, Reference and Maximum currents as follows:
Basic Current (Ib) Direct Connected
Reference Current (In) CT Operated
Direct Connected Maximum current (Imax) shall preferably be an integral multiple of Ib.
Direct Connected A1120/A1140 meters may have Imax values up to a maximum of 100A
CT Operated shall have maximum currents of 1.2 In, 1.5 In and 2 In
CT Operated A1120/A1140 meters may be:
1 - 2A (suitable for use as 1 - 1.2A, 1 - 1.5A, or 1 - 2A)
5 - 10A (suitable for use as 5 - 6A, 5 - 7.5A, or 5 - 10A)
1 - 10A (suitable for use with any of the above 6 ratings)
EN 50470-1 (MID) defines basic values or Itr from which Imin, Iref and Imax can be derived
Imin, Iref and Imax have been chosen so that the following relationships are met
Note 2: VOLTAGE RATINGS
Of the values IEC/EN 62052-11 defines for reference voltages, the following may be accepted
Ref Voltages for meters not connected through current transformers
EN 50470- 1 (MID) defines for reference voltages, the following standards and exceptional values
Ref Voltages for Direct Connected
Meters with marked currents and voltages other than the above values CANNOT be provided when the nameplate
shows the IEC/EN Standard Number.
If a valid requirement exists for meters with marked values within the acceptable ranges, but not listed above, specific
arrangements to provide nameplates not showing the IEC/EN standard must be made.
Note 3: TEST INDICATOR OUTPUT VALUES
The following values are to be used for the Test Indicator LED outputs:
Direct Connected: 1,000 p/kWh (kvarh)
Note 4: SCHEME COMPATIBILITY
Schemes generated for VERSION 'A' meters are not compatible with VERSION 'C' meters
Note 5: SPECIAL ADDITIONS
Early issues of this code used the final (16
voltage terminals".
Figure 1 - Model Code (Continued)
© Elster Metering Limited - M181 001 2G - 5/2010
Basic values of Itr
Basic values of Itr
Direct Connected, Class A
CT Operated, Class A
Direct Connected, Class B
CT Operated, Class B
Std values
Exceptional values
Std values
Exceptional values
th
) digit for SPECIAL ADDITIONS and an 'A' in this position indicates "with additional
Standard values: 5, 10, 15, 20, 30, 40, 50A Exceptional
values: 80A.
Standard values: 1, 2, 5A
Exceptional values: 1.5, 2.5A
Direct Connected
0.5, 1, 1.5, 2A
CT Operated
0.05, 0.1, 0.25
Imin < 0.5 x Itr
Iref = 10 x Itr
Imin < 0.4 x Itr
In = 20 x Itr
Imin < 0.5 x Itr
Iref = 10 x Itr
Imin < 0.2 x Itr
In = 20 x Itr
120, 230, 400V
100, 127, 200, 220, 240, 380, 415V
230/400V
220/380V, 240/415V
CT Operated:
Imax > 50 x Itr
Imax > 1.2 x In
Imax > 50 x Itr
Imax > 1.2 x In
10,000 p/kWh (kvarh)
-
A
-
C
F
G
Q
K
B
Z
N
A
N