Page 1
33333333333 A100C BS Electronic Single Phase Meter Operating & Maintenance Instructions Meter Variants All variants are available with IrDA or IEC 62056-21 communications • Import kWh - one rate • Import kWh - two rate • Import kWh, Power flow insensitive - one rate •...
Page 3
A100C Single Phase Meter Operating & Maintenance Instructions M130 300 2C 5.2007 Other Products in this Series A100C DIN Electronic single phase meter M130 300 1 A102C BS Electronic Single Phase Meter M130 400 1 with kvarh measurement capability A102C DIN...
The purchaser is responsible for making sure that everyone, whether in his employment or not, who will be associated with the products supplied by Elster Metering Systems, and to which these instructions and information apply, are made familiar with the contents of this manual.
The CE Mark does not denote compliance with the European Low Voltage Directive 73/23/EEC, which specifically excludes electricity meters. The A100C meter measures active energy according to the requirements of EN 62053- 21:2003 for indoor kWh meters of protective Class II and accuracy Class 1 or 2.
_____________________________________________________________________________________ APPROVALS Variables of the A100C are approved by the Office of Gas and Electricity Markets (OFGEM) in compliance with European and British metering legislation (Approval Number 984). These are identified in the model code. Other variants will be approved by...
GENERAL DESCRIPTION Basic Meter Types SJ… BS Case Current Ratings The A100C can be supplied for use with 120V or 230V single phase two wire systems at 50 or 60Hz. The following current ratings and pulses/kWh are available: OFGEM Approved A100C...
Connection diagrams are shown inside the terminal cover. Meter Accuracy The A100C measures active energy in accordance with the requirements of IEC 62053- 21:2003 for indoor kWh meters of protective Class II and accuracy Class 1 or Class 2. Typical accuracy curves are shown in Figure 4.
Operating & Maintenance Instructions _____________________________________________________________________________________ TEST INDICATOR A red test output LED is provided which pulses in accordance to the following configurations: Import only meter: The LED pulses for forward energy only Import meter with Power Flow Insensitive enabled: The LED pulses for forward and reverse energy Import/export meter: The LED pulses for forward and reverse energy The LED is permanently illuminated when in anti-creep (i.e.
12.1 Introduction The A100C meter is fitted with a high contrast, wide viewing angle liquid crystal display with seven large digits (9.8mm x 3.5mm). The smaller digit (reference indicator) may identify the parameters being displayed. Seven chevrons identify displayed information.
Page 17
Operating & Maintenance Instructions _____________________________________________________________________________________ Count Reverse run/Power fail The Reverse Run Count display is shown below (for export meters the display shows the number of instances the meter has been exporting). Chevrons Reference id 4 - Count 1 - Reverse Run (Max 255) 2 - Power Fail (Max 65535) Hours The following durations can be displayed:...
Operating & Maintenance Instructions _____________________________________________________________________________________ 2 Rate kWh – normal operation Chevron 1 indicates kWh for Rate 1, Rate 2 or cumulative is displayed. The 'reference id' identifies the rate being displayed. Chevron 3 indicates that reverse energy is being displayed (optional). Chevron 7 indicates when the rate displayed is currently active. Chevrons Reference id 1 - kWh...
_____________________________________________________________________________________ COMMUNICATIONS The A100C has the option of IrDA or optical IEC 62056 -21 (Formerly IEC 1107) communications. Both methods of communication allow the meter registers and security data to be read electronically by a laptop or hand held device, greatly reducing the possibility of manual reading errors.
Operating & Maintenance Instructions _____________________________________________________________________________________ PULSING OUTPUT 14.1 Output Configurations An opto-isolated pulsing output can be provided as an option. The output is available via the meter auxiliary terminals in the following configurations: Single rate meter - The output is connected to the meter's two auxiliary terminals and is fully isolated.
Check that there is no movement or loose parts within the meter enclosure. If damage has been sustained in transit, an immediate claim should be made to the Transport Company, and a report sent to the Elster Metering Systems branch office or agent.
Operating & Maintenance Instructions _____________________________________________________________________________________ COMMISSIONING WARNING Commissioning must only be carried out by appropriately trained and qualified personnel. Check that the supply rating on the meter nameplate corresponds to the system rating. With the system de-energised, check the cable connections are secure and correct to the wiring diagram fitted under the terminal cover Refit and seal the terminal cover.
Operating & Maintenance Instructions _____________________________________________________________________________________ Note 1:- IEC62052-11 (to which IEC62053-21 refers) defines only Basic and Maximum currents as follows: Basic Current (Ib) Direct Connected Standard values: 5, 10, 15, 20, 30, 40, 50A Exceptional values: 80A and states that Maximum current (Imax) is preferably an integral multiple of Ib: BS meters shall preferably be an integral multiple of Ib up to a maximum of 100A (e.g.
Operating & Maintenance Instructions _____________________________________________________________________________________ Typical wiring diagrams Single rate Two rate Single rate – SO output MAIN LOAD MAIN LOAD MAIN LOAD Two rate - SO non-isolated output Auxiliary Terminal Numbering Terminal numbers Configuration One Rate, no SO Two Rate One Rate, Isolated SO Two Rate, Non Isolated SO LOAD...
APPENDIX A IrDA Data Serial Output The A100C’s IrDA port and optional Serial Data Port are transmit only. The ports transmit billing, security and status data once every second. The data rate is programmed at time of manufacture and is dependent on the meter port configuration.
Page 41
Operating & Maintenance Instructions _____________________________________________________________________________________ FIELD NAME Format Description Error Flags Bit field Error flags: Bit 7-6: Reserved. Bit 5: ROM checksum error, 0 = no error, 1 = error. Bit 4: Table 1 checksum error; 0 = no error, 1 = error. Bit 3: Table 0 checksum error;...
_____________________________________________________________________________________ APPENDIX B - Checking kWh Registration Accuracy Introduction Various methods of checking kWh accuracy of registration of the A100C meter are available. Methods using the LED and Register advances are described below. Checking Meter Accuracy Using the Test LED The meter test LED is configured at manufacture to pulse for import kWh (import only meter) or pulse for import plus export kWh (import/export or power flow insensitive meters).
IrDA Receiver - This must be set to the same baud rate as the meter Laptop or PC IrDA Software - Various software packages are available. The software package described is available from Elster Metering Systems. It is that suggested this software is installed in a folder called A100C. B3.2.1...
APPENDIX C - IrDA Data Software Introduction Elster Metering System IrDA Software allows meter register data, security data and identification data to be collected via the IrDA port. It is suggested the software is installed in a folder called A100C.
Page 47
Operating & Maintenance Instructions _____________________________________________________________________________________ Registration The following information is displayed: Register 1, Register 2 and Register 3 readings for Rate 1 and Rate 2 The register sources The current four quadrant measurement The Power factor Security The following information is displayed: System Errors System Status Total time powered...
Page 50
About Elster Group Elster Group is the world’s leading manufacturer and supplier of highly accurate, high quality, integrated metering and utilisation solutions to the gas, electricity and water industries. In addition, through its subsidiary Ipsen International, it is the leading...