Download Print this page
Elster ALPHA Installation Instructions Manual
Elster ALPHA Installation Instructions Manual

Elster ALPHA Installation Instructions Manual

Socket-connected / bottom-connected single phase/ polyphase watthour meters

Advertisement

Quick Links

ALPHA meter
Installation instructions
IL42-4001S
General
This instructional leaflet contains general installation instructions for the following single phase and
polyphase watthour meters:
• socket-connected meters: 1S, 2S, 3S, 4S, 5S, 6S, 8S, 9S, 10S, 12S, 13S, 16S, 26S, 29S, 35S, 36S, 45S, 56S
• bottom-connected meters: 5A, 6A, 10A, 13A, 16A, 35A, 36A, 45A
See the following technical manuals for more information about the ALPHA meter:
• ALPHA
Meter Technical Manual (TM42-2180A or later)
®
• ALPHA Meter Options Technical Manual (TM42-2181B or later)
• ALPHA Plus
Meter Technical Manual (TM42-2182C or later)
®
• A3 ALPHA Meter Technical Manual (TM42-2190A or later)
All meters are calibrated and tested before shipment. For proper installation, accuracy, and maximum
life of the meters, use the following installation procedures.
Use authorized utility procedures to install and service metering equipment. Dangerous voltages are
present. Equipment damage, personal injury, or death can result if safety precautions are not
followed.
Use circuit closing devices on any current transformer secondaries (3S, 4S, 5S, 5A, 6S, 6A, 8S, 9S, 10S,
10A, 26S, 29S, 35S, 35A, 36S, and 36A meters). Equipment damage, personal injury, or death can
result if circuit closing devices are not used.
Form 45S, Form 45A, and Form 56S meters present additional risks of electrical shock that may result
in severe personal injury or death when the cover is removed from energized meters unless certain
additional safety procedures and precautions are followed. Be sure to follow the safety procedures
and precautions when servicing Form 45S, Form 45A, and Form 56S meters as stated in this manual
(see "Forms 45S, 45A, and 56S safety precautions" on page 3) as well as your authorized utility
procedures.

Advertisement

loading

Summary of Contents for Elster ALPHA

  • Page 1 • socket-connected meters: 1S, 2S, 3S, 4S, 5S, 6S, 8S, 9S, 10S, 12S, 13S, 16S, 26S, 29S, 35S, 36S, 45S, 56S • bottom-connected meters: 5A, 6A, 10A, 13A, 16A, 35A, 36A, 45A See the following technical manuals for more information about the ALPHA meter: • ALPHA Meter Technical Manual (TM42-2180A or later) ®...
  • Page 2 - For 150 amp meters, use #1 AWG or 50 mm2 wiring (or in accordance with standard utility operating practices) - For transformer rated meters, use #9 wiring (or in accordance with standard utility operating practices) Not supplied by Elster Solutions.
  • Page 3 ALPHA meter IL42-4001S After you install a bottom-connected meter, check the following: • If load is applied, check that the pulse arrows on the LCD are blinking. The LCD has 2 sets of pulse arrows, one located above the other. The upper set of arrows indicates watthours, and the lower set indicates alternate energy (kVARh or kVAh, if available).
  • Page 4: Installation Wiring

    IL42-4001S Installation wiring All available ALPHA meter forms are listed and separated with respect to the type of service being metered. Use of Form 9S, 10S, and 10A (in 8S and 8A applications), and Form 16S (in Form 15S application) are also shown. Form 14S and 14A applications are simply 4 wire WYE services and would be metered by Form 16S and 16A.
  • Page 5 ALPHA meter IL42-4001S 3 wire delta meters Form 5S Form 5A Form 12S 3 phase, 3 wire delta, self–contained 3 phase, 3 wire delta, 2 CTs, 0 or 2 PTs 3 phase, 3 wire delta, 2 CTs, 0 or 2 PTs...
  • Page 6 ALPHA meter IL42-4001S 3 wire delta meters Form 45A Form 56S 3 phase, 3 wire delta, 2 CTs, 0 or 2 PTs 3 phase, 3 wire delta, 2 CTs, 0 or 2 PTs CIRCUIT CLOSING DEVICE 3 wire wye meters...
  • Page 7 ALPHA meter IL42-4001S 3 wire wye meters Form 35S Form 35A Form 45S 2 phase, 3 wire wye, 2 CTs, no PTs 2 phase, 3 wire wye, 2 CTs, no PTs 2 phase, 3 wire wye, 2 CTs, no PTs...
  • Page 8 CIRCUIT CIRCUIT CLOSING CLOSING DEVICE DEVICE 60 Hz only Reduce CT ratio ALPHA Plus with by ½ autodetection enabled & Reduce CT ratio by ½ A3 ALPHA only Form 35S Form 35S Form 35A 3 phase, 4 wire delta, 2 CTs, 2 PTs...
  • Page 9 3 phase, 4 wire delta, 2 CTs, no PTs 3 phase, 4 wire delta, 2 CTs, no PTs 60 Hz only ALPHA Plus with autodetection enabled & A3 ALPHA only CIRCUIT CLOSING DEVICE Reduce CT ratio by ½ Reduce CT ratio by ½ Reduce CT ratio by ½...
  • Page 10 ALPHA meter IL42-4001S 4 wire wye meters Form 6A Form 9S Form 10S (Form 9S application) 3 phase, 4 wire wye, 3 CTs, 0 or 2 PTs 3 phase, 4 wire wye, 3 CTs, 0 or 3 PTs 3 phase, 4 wire wye, 3 CTs, 0 or 3 PTs...
  • Page 11 ALPHA meter IL42-4001S 4 wire wye meters Form 35A Form 36S Form 36A 3 phase, 4 wire wye, 3 CTs, 0 or 2 PTs 3 phase, 4 wire wye, 3 CTs, 0 or 2 PTs 3 phase, 4 wire wye, 3 CTs, 0 or 2 PTs...
  • Page 12: Battery Installation And Replacement

    - All relays are fully programmable. Sources for the relays can be any basic metered quantity, EOI, load control, PQM test failure, or relay-related alarm condition. See the A3 ALPHA Meter Technical Manual (TM422190B or later) and the Metercat User Guide (TM42-2204B or later) for specific...
  • Page 13 Orange RELAY E Programmable COMMON NO Brown RELAY F Load control Programmable COMMON Green Figure 3. Color coding for 4 relays with 9 output leads A3 ALPHA only Yellow Black RELAY A Programmable COMMON Wht/Blk Blue Programmable RELAY B COMMON...
  • Page 14 ALPHA meter IL42-4001S Figure 4. Color coding for 6 relays with 12 output leads ALPHA & A3 ALPHA ALPHA Plus Yellow KYZ1 Programmable RELAY A Black kWh delivered Wht/Blk Programmable as Programmable RELAY B Blue KYZ2, LC, or EOI Violet...
  • Page 15: Industry Canada Compliance

    (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation of the device. Warning (Part 15.21) Changes or modifications not expressly approved by Elster could void the user's authority to operate the equipment. Industry Canada compliance This Class B digital apparatus complies with Canadian ICES-003.
  • Page 16 In no event will Elster Solutions, LLC be responsible to the user in contract, in tort (including negligence), strict liability or otherwise for any special,...