Type Codes for Input Devices
Type Code
MONITOR
PULL STATION
RF MON MODUL
RF PULL STA
SMOKE CONVEN
SMOKE DETECT
WATERFLOW
WATERFLOW S
ACCESS MONTR
AREA MONITOR
AUDIO SYSTEM
EQUIP MONITR
RF SUPERVSRY
SECURITY
LATCH SUPERV
TRACK SUPERV
SPRINKLR SYS
SYS MONITOR
TAMPER
ACK SWITCH
ALLCALL PAGE
DRILL SWITCH
EVACUATE SWITCH non-alarm
FIRE CONTROL
NON FIRE
PAS INHIBIT
POWER MONITR
RESET SWITCH
SIL SWITCH
TELE PAGE
TROUBLE MON
ABORT SWITCH
MAN RELEASE
MANREL DELAY
SECOND SHOT
Blank
HEAT DETECT
NFS-640 Programming Manual P/N 51333:B 10/03/2003
www.PDF-Zoo.com

Type Codes for Monitor Modules

A list of monitor module Type Codes, which you can use to change the function of a monitor module
point.
Point Characteristics
Point
Latching
Point Function
(Y/N)
Type
fire alarm
Y
Lights fire alarm LED and activates CBE
fire alarm
Y
Lights fire alarm LED and activates CBE
fire alarm
Y
Lights fire alarm LED and activates CBE
fire alarm
Y
Lights fire alarm LED and activates CBE
fire alarm
Y
Lights fire alarm LED and activates CBE
fire alarm
Y
Lights fire alarm LED and activates CBE
fire alarm
Y
Lights fire alarm LED and activates CBE
supervisory
Y
Lights supervisory LED and activates
CBE
non-alarm
N
Activates CBE
security
Y
Lights security LED and activates CBE
trouble
N
Activates CBE and lights trouble LED
trouble
N
Activates CBE and lights trouble LED
supervisory
N
Lights Supervisory LED
security
Y
Lights security LED
supervisory
Y
Lights supervisory LED
supervisory
N
Lights supervisory LED
supervisory
Y
Lights supervisory LED
security
Y
Lights security LED and activates CBE
supervisory
Y
Lights supervisory LED, activates CBE
non-alarm
N
Emulates panel Acknowledge switch, no
CBE
non-alarm
N
Activates all speaker circuits, no CBE
non-alarm
N
Emulates panel Drill switch
N
Emulates keypad Drill Switch
non-alarm
Y
Activates CBE
non-alarm
N
Activates CBE
non-alarm
N
Inhibits Positive Alarm Sequence
trouble
N
Indicates trouble, activates CBE
non-alarm
N
Emulates keypad Reset switch
non alarm
N
Emulates keypad Signal Silence switch
non-alarm
N
Emulates Page Button on FFT-7
trouble
N
Indicates Trouble and activates CBE
non alarm
N
Indicates Active at the panel
fire alarm
Y
Lights Fire Alarm LED and activates
CBE
fire alarm
Y
Lights Fire Alarm LED and activates
CBE
fire alarm
Y
Indicates Active at the panel and activates
CBE
fire alarm
Y
Lights fire alarm LED and activates CBE
fire alarm
Y
Lights fire alarm LED and activates CBE
Table 33 Type Codes for Monitor Modules
Appendix F: Type Codes
Device Function
Alarm-monitoring device
Manual fire-alarm-activating device, such as a pull station
Wireless alarm-monitoring device
Wireless manual fire-alarm-activating device, such as a pull station
Indicates activation of a conventional smoke detector
attached to an FZM-1
Indicates activation of a conventional smoke detector
attached to an FZM-1
Monitor for waterflow alarm switch
Indicates supervisory condition for activated waterflow switch
Used for monitoring building access
Monitors building access
Used for monitoring audio equipment
Used for recording access to monitored equipment
Monitors a radio frequency device
Indicates activation of security alarm
Indicates latching supervisory condition
Monitors for waterflow tamper switches for alarm points
Monitors a waterflow device
Monitors equipment security
Indicates activation of tamper switch
Silences panel sounder, gives an Acknowledge message
on the panel LCD
Emulates AMG-1 All-call switch
Activates silenceable outputs
Activates all silenceable outputs
Used for non-fire activation of outputs
Used for building energy management
Inhibits Positive Alarm Sequence
Monitors auxiliary power supplies
Resets control panel
Turns off all activated silenceable outputs
Allows remote paging to a fire area
Monitors trouble inputs
Aborts activation of a releasing zone
Indicates activation of a monitor module programmed to
releasing zone to perform a releasing function
Indicates activation of a monitor module programmed for
a release output
Provides second activation of releasing zone after soak
timer has expired.
Monitors for a device with no description
Monitors for conventional heat detector
105

Advertisement

Table of Contents
loading