How to Use the Basic Program
NFS-640 Programming Manual P/N 51333:B 10/03/2003
www.PDF-Zoo.com
F7 (Holiday) The Holiday screen provides fields for specifying up to nine holiday dates. For details on
holiday selections, refer to "Time Control Zones" on page 82. From the Special Function Change
screen, press F7 to display the Holiday screen:
PRG HOLIDAY FUNC
**/**
F8 (Coding Function) The Coding Function screen provides fields for specifying one of seven
coding functions: March Time, Two-stage, California, Temporal, Canadian Two-Stage (3 minutes),
Canadian Two-Stage (5 minutes), and System Sensor Strobe. For details on selecting coding functions,
refer to "Coding Functions for NACS and Panel Circuits" on page 82. From the Special Function
Change screen, press F8 to display the Coding Function screen:
PRG CODING FUNCTION CODE TYPE
MARCH TIME
F9 (Pre-Alarm) The Pre-Alarm screen provides fields for programming the Alert or Action Pre-Alarm
functions. For details on Pre-Alarm selections, refer to "Pre-Alarm" on page 88. From the Special
Function Change screen, press F9 to display the Pre-Alarm screen:
Pre-Alarm programming
status banner
PRG PRE-ALARM FUNCT
Holiday programming status banner
**/**
**/**
**/**
**/**
Nine fields for selecting holidays:
USA time (mm/dd)
Coding Function programming status banner
Coding Function selection (refer to
"Coding Functions for NACS and
Panel Circuits" on page 82)
ACTION or ALERT Pre-Alarm level: press the
key to toggle between ALERT and ACTION. For details on
selections, refer to "How to Select a Pre-Alarm Level" on page 89)
**/**
**/**
**/**
**/**
F08
Coding Function
(Zone F8)
or
NEXT
PREVIOUS
ALERT
F09
Pre-Alarm (Zone F9)