Battery Type And Capacities - Notifier IFS-2600 Operation, Installation, And Maintenance Manual

Hide thumbs Also See for IFS-2600:
Table of Contents

Advertisement

IFS-2600 Fire Indicator Panel
Important Notes:
When using external power supply, JP1 link on IFS2006E must be fitted to enable external PSU
monitoring.
If this supply is used to power a NI-2008 gas module, the following additional components are required
to ensure a break free change over from the mains supply to the panel battery in case of mains fail
condition.
1. A 6A4 or P600G rectifier diode (Notifier part number #266) is to be installed in series with the external
+27V output of the IFS-2600 termination board.
2. A 3300µF 50V Electrolytic Capacitor (Notifier part number #1248) should be installed across
the +27V and 0V of the ancillary device.
OUTPUT
EXTERNAL
POWER
SUPPLY

4.4.3. Battery Type and Capacities

In general, any Sealed Lead Acid (SLA) Battery, or Wet Lead Acid Battery designed for stationary use is
compatible with the IFS-2600 Fire Indicator Panel. Automotive batteries must not be used. The use of
Nickel Cadmium batteries is not recommended.
Manufacturer
Olympic Batteries
Olympic Batteries
Olympic Batteries
Olympic Batteries
Olympic Batteries
Olympic Batteries
Olympic Batteries
Olympic Batteries
CAUTION:
DOC-01-009
This applies to IFS-2005/IFS-2006 Boards without ECN09-034 modification!!
AC
REMOTE
REMOTE
INPUT
OUTPUT
INPUT
24V 0V
24V 0V
Type
Number
SLA
CJ12-7
SLA
CJ12-12
SLA
CJ12-18
SLA
CJ12-26
SLA
CJ12-33
SLA
CJ12-40
SLA
CJ12-85
SLA
CJ12-100
Table 4-4, Battery Capacities
Risk of explosion if battery is replaced by an incorrect type.
Dispose of used batteries according to Manufacturer Instructions
BATT
INPUT
+
-
6A4
3300uF
Voltage
Capacity (Ah)
12
7
12
12
12
18
12
26
12
33
12
40
12
85
12
100
Section 4 Installation
POWER IN
NI-2008 GAS
SUPPRESSION
MODULE
Qty Required
2
2
2
2
2
2
2
2
25